Single Phase Electrical and Ditital Energy Meters Calibration

Customization: Available
Warranty: Three Years
Application: Mechanical Instrument, Electromagnetic Instrument

Products Details

  • Overview
  • Product Description
  • Product Parameters
  • Detailed Photos
Overview

Basic Info.

Model NO.
GF112
LCD Display
With LCD Display
Customized
Customized
Active Power Measurement Accuracy
0.3%, 0.5%
Energy Measurement Accuracy
0.3%, 0.5%
Power Supply
AC 110-264V 50/60Hz
Warming-up Time
< 5min
Power Consumption
≤5va
U Range
0-264V
I Range
10mA-40A or 10mA-120A
Frequency Measurement Range
45-65Hz
Pulse Constant
900
Input Range of Pulse Constant
1-25000
Transport Package
Standard Export Wooden Box
Specification
185mm× 67mm× 30mm
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
200units/Day

Product Description

GF112 single phase electrical and ditital energy meters calibration
Product Description

 


GF112 single phase electrical and ditital energy meters calibration is with human oriented design, hand-held and lightweight. It is suit for electric power departments, measuring and quality examining departments and electric lab to field use. It is capable of testing various types single phase meters on site and can also be used for testing alternating current parameters.
Features
1. Field test kinds of inductive, electronic single phase meter
2. Measurement error, voltage, current, power, power factor and frequency at site
3. LCD color display, English menu, direct viewing and convenient
4. Equip with RS232 to connect with PC
5. With built-in 5A load
6. Energy accumulation function
7. Large capacity storage device for mass memory
8. With 2pcs clamp CT to test ratio of current transformer (option)
Product Parameters

 

lectrical parameters  
Active power measurement accuracy 0.3%, 0.5%
Energy measurement accuracy 0.3%, 0.5%
Power supply AC 110-264V 50/60Hz
Warming-up time < 5 min
Power consumption ≤5VA
Voltage measurement
Range 0-264V
Accuracy 0.30%
Current measurement
Range 10mA-40A or 10mA-120A
Accuracy 0.3%
Phase measurement
Range 0°-359.9°
Resolution 0.1°
Accuracy 0.5° 
Frequency measurement
Range 45-65 Hz
Resolution 0.01Hz
Accuracy 0.05Hz
Power factor measurement
Range 0.4000 ~ +1.0000
Resolution 0.001
Accuracy 0.01
Electric energy pulse output 
Pulse constant 900
Energy pulseinput
Input range of pulse constant 1-25000
Pulse input level 5V
Mechanical parameters
Dimensions (W×D×H) (mm) 185×67×30
Weight (kg) 1 (mains)
2 (appendix and bag) 
Environmental conditions
Working temperature -10°C to 50°C
Working humidity 5%- 85%RHD
Storage temperature -25°C to 70°C
Storage humidity 5% -95%RHD
Detailed Photos

 