- Overview
- Product Description
- Features
- Product Parameters
- Detailed Photos
Basic Info.
Model NO.
GF312D1
Customized
Customized
Accuracy
0.05% or 0.1%
Clamp CT
Standard 100A
Current
0~20A
Voltage
0~480V
Gf312D1
Handheld Three Phase Kwh Meter Field Calibrator
Transport Package
Standard Export Carton
Specification
CE, ISO9001: 2008, IEC
Trademark
GFUVE
Origin
Beijing, China
HS Code
90308490
Production Capacity
200units/Month
Product Description
The instrument is a precision AC energy meter testing instrument, mainly used to test three phase energy meter error on site and measure various of AC parameters.
W Three phase active or reactive electricity energy meter;
W Calibrate three phase, single phase, active or reactive meter error;
W Measure U(voltage) of three phase or single phase;
W Measure I(current) of three phase or single phase;
W Measure active power of three phase or single phase;
W Measure reactive power of three phase or single phase;
W Measure apparent power of three phase or single phase;
W Measure power factor of three phase or single phase;
W Measure phase angle between voltage and current;
W Measure frequency of power line;
W Display vector diagram;
W Display waveform of U and I;
W Analyze and display content of harmonic of U and I;
W Store and display measured data;
W Optional 5A, 20A, 100A, 500A, 1000A, 2000A, 3000A current clamp;
W Measure CT variable ratio;
W Measure the ratio or lag-angle of low-voltage transformer.
W Adopt 32 bit ARM processor, multi-channel 16 bit precision A/D convertor, high resolution TFT color LCD;
W Inner equipped with 0.01% wide-range current transformer and can be equipped with various type current clamps, wide range of measurement and high veracity.
W Low consumption circuit design, high energy Li batter supply, intellectual power management software, which make the instrument can continuously work up to 10 hours.
Test Voltage | |
Range | 5V - 480V |
Error | ± 0.05% (30V - 480V) ± 0.1% (5V - 30V) |
Harmonic | 2 nd -- 63 st |
Test Current | |
Range (direct connection) | 5mA - 20A |
Error (direct connection) | ± 0.05% (100mA - 20A) ± 0.1% (10mA - 100mA) |
Range (Clamp CT) | 10mA - 3000A |
Error (Clamp CT) | ± 0.2% (100mA - 3000A) ± 0.5% (10mA - 100mA) |
Harmonic | 2 nd -- 63 st |
Power measure error | |
Active power (direct connection) | ± 0.05% (0.1A - 20A) ± 0.1% (0.01A - 0.1A) |
Reactive power (direct connection) | ± 0.1% (0.1A - 20A) |
Energy measure error | |
Active energy (direct connection) | ± 0.05% (0.1A - 20A) ± 0.1% (0.01A - 0.1A) |
Reactive energy (direct connection) | ± 0.1% (0.1A - 20A) |
Phase angle | |
Range | 0º - 360º |
Error | ± 0.05º |
Frequency | |
Range | 45Hz - 65Hz |
Pulse output | |
Energy constant | 180000imp/kWh1800imp/kWh18imp/kWh |
Pulse ratio | 1: 1 |
Output level | 5V |
Pulse input | |
Input channel | 1 |
Input level | 5 - 24V |
Input frequency | Max. 2MHz |
Display | |
Resolution | 6" TFT (640× 480) |
Function | |
Vector diagram | Yes |
Waveform | Yes |
Energy accumulation | Yes |
Communication port | RS232 |
Communication with PC | Yes |
Other | |
Voltage Supply way | External power |
Voltage Supply 1 | 220V ± 10%, 50/60Hz ± 2Hz |
Voltage Supply 2 | Li-polymer battery, size: 110X51X16mm Nominal output voltage: 7.2V, Capacity: 5000mAh. |
Ambient temperature | -10 -- 55degrees |
Relative humidity | 15% -- 85% |
Instrument Dimensions (W × H × D) (mm) | 245× 162× 60 |
Carry Case Dimensions (W × H × D) (mm) | 450× 320× 185 |
Weight (kg) | 1.7kg |